RMI / EMI Shielded Room - Global EMC

RF Shielded Rooms


In almost all modern buildings, high levels of wireless RF signals are present from Wi-Fi, Radio, mobile phone transmitters, wireless CCTV cameras and intruder alarm systems. Global EMC’s RF Shielded Rooms work on the Faraday cage principle of a 6 sided metal enclosure, providing a controlled environment, free from electromagnetic interference (EMI) and ambient RF noise from entering or exiting the room.

This provides a suitable location for research and development, sensitive product testing or conducted EMC testing.
A turnkey solution is provided by Global EMC to specify, design, manufacture, install and provide final certification and testing of the complete project. High-quality internal finishes are also provided including lighting, power, data and HVAC to make the RF Shielded Rooms durable, practical and comfortable.

Contact us for more Information

Choose This Test Chamber For

Shield Effectiveness - Global EMC

Certification

Independently verified to be compliant to MIL-STD-285, IEC EN 50147-1 and IEEE 299 standards.

Fully Anechoic Room (FAR) Fully Anechoic Chamber (FAC) - Global EMC

Anechoic Chambers

Providing RF shielding for anechoic chambers, control rooms and amplifier rooms.

Research and Development - Global EMC

Analysis

Experimentation, research and development, product analysis, sensitive measurements and testing.

WiFi - Global EMC

Pollution

Removal of unwanted ambient background signals and noise, to allow an environment free from electromagnetic interference.

Simplicity in Flexibility

[vc_headings style="theme2" borderwidth="3" borderclr="#3ec7ff" title="Simplicity in Flexibility" align="left" use_theme_fonts="yes" titlesize="28" titleclr="#000000"]All of our RF Shielded Rooms are designed and individually manufactured by Global EMC, enabling every installation to be bespoke and uniquely shaped to exact requirements and specifications.   The shield is constructed from pre-fabricated modular panels, each panel is fitted together on-site to form a completely “sealed” six-sided enclosure. The flexible modular system enables almost any size and shape of the room to be created. Installed as a self-supporting free standing room or architectural shielding fitted onto an existing room, the enclosures can be sized to fit the host building and maximise the usable space.   The installation has no hot works or welding and can easily be disassembled and re-located. The external façade is finished with a premium quality finish to match the client’s company colours or simply complement the surrounding space.[/vc_headings]

All of our RF Shielded Rooms are designed and individually manufactured by Global EMC, enabling every installation to be bespoke and uniquely shaped to exact requirements and specifications.

The shield is constructed from pre-fabricated modular panels, each panel is fitted together on-site to form a completely “sealed” six-sided enclosure. The flexible modular system enables almost any size and shape of the room to be created. Installed as a self-supporting free standing room or architectural shielding fitted onto an existing room, the enclosures can be sized to fit the host building and maximise the usable space.

The installation has no hot works or welding and can easily be disassembled and re-located. The external façade is finished with a premium quality finish to match the client’s company colours or simply complement the surrounding space.

Finishing Touches

Upon the completion of our RF Shielded Rooms numerous options are available to tailor the shielded room to exact requirements. Rooms can be left as a bare shield for an industrial and durable finish or lined with plasterboard, melamine board or cleanroom finishes.

Office-style interiors are available including vinyl, anti-static or carpeted floors, dimmable lighting, mains power, data and furniture. For telecommunications or IT networks, raised false flooring can be provided, server cabinets and air conditioning.

To ensure the integrity of the shield, all penetrations are accounted for as required. Fire alarm, air conditioning, cameras, compressed air are just some of the limitless possibilities that can be integrated into the shield.

Shielding Effectiveness tested to EN 50147-1

Every Global EMC shielded room is provided with a Faraday cage shield. The shielded enclosure provides both an area free from external ambient signals but also can be used for devices inside the room from transmitting outside the shielding. Such as in Forensic investigation rooms

The measure of shielding performance is conventionally known as “shielding effectiveness”. 100dB in plane and microwave frequencies is generally regarded by most standards as a very high level of shielding suitable for scientific use.

Global EMC offer two levels of shielding Standard and Extended Performance. Standard performance is suitable for most shielding requirements and is typically seen in commercial testing situations. Extended Performance is usually used in high-performance Military applications along with certain high frequency needs.

Key Features

Ultra-high shielding performance as standard.

Shielding effectiveness to EN 50147-1 and IEEE299.

Standard shield performance of 60dB @ 10 kHz, 100dB @ 300 kHz, 100dB @ 1-10 GHz. 80dB @ 18GHz

Advanced (Optional) shield performance of 80dB @ 10 kHz, 100dB @ 100 kHz - 40 GHz

Bespoke solution upon request. Test facility can be configured to your exact requirements.

Designed and manufactured to the highest standards in Great Britain.

Designs created in Solidworks® and AutoCAD to ensure ideal configuration and coordination.

All materials are shipped in component form and fit through a standard doorway for ease of installation.

Can be provided for self-assembly.

Fibre optic or dimmable LED lighting.

Industry-leading low maintenance shielded door with copper-beryllium knife-edge seals.
Full Specification

External DimensionsTo customer requirements*.

Shielded Pedestrian Door (Clear Opening)900mm - 1200mm (W) x 2000mm (H)*

Steel StructureSelf-supporting structure to industry standards.

Floor Loading (Standard)1 Ton/M².

Access RampAvailable if required.

Power and Lighting installationAvailable as required.

Filters1 x 32A 230V Single phase (2 line).

Honeycomb Vents2 x 300mm (W) x 300mm (H) (static air).

Independent shieldTest included.

Additional Options Include:
CCTV, Office finish, waveguides, double doors, automated doors, Fire detection, raised floor, HVAC, Fibre optic lighting, additional power filters & data filters.
*All dimensions and configurations can be altered upon request (subject to compatibility).